The HI21211 controller is a dual set point, microprocessor-based pH process controller specifically designed to meet your process control requirements. A host of self testing features and user-friendly functions make HI21211 a great value.
- On/Off Control
- Fail Safe Alarm System.
- Automatic Temperature Compensation using pt100 temperature probe.
Fail Safe Alarm System
- Hanna’s exclusive Fail Safe Alarm System protects against problems caused by power supply failure or signal interruption, which are typical risks in industrial environments. An alarm condition is indicated by a red LED, located directly on the front panel of the controller.
Simple Installation
- HI21211 has mounting holes molded into the housing to assure simple, quick and secure installation without the need for additional hardware.
Isolated Recorder Output
- To enhance troubleshooting and the ability to record data while monitoring, simply attach a recording device to the instrument’s 4 to 20 mA output contacts, conveniently located on the front panel, to obtain a copy of the results on demand.
Matching Pin
- A differential input prevents problems due to ground loop current when using pH electrodes with a matching pin. Very effective at extending the life of the electrode.
Quality Construction
- Housed in a rugged, modular, fiber-reinforced polypropylene housing that will resist the harmful effects of most chemicals.
Password Protection
- The Hanna password protection feature keeps these controllers safe from tampering. Only users with the proper password can change the settings of these controllers.
SKU | HI21211-2 |
---|---|
Product Name | Wall Mounted pH Digital Controller with Dual Setpoint - HI21211 |
Quote Required | Yes |
pH Range | 0.00 to 14.00 pH |
pH Resolution | 0.01 pH |
pH Accuracy | ±0.02 pH |
pH Calibration | automatic, one, two or three point, at pH 4.01, 7.01, 10.01 |
pH Temperature Compensation | automatic (with Pt100 probe) or manual from -9.9 to 120°C |
pH Dosing Relay | electromechanical relay SPDT contact outputs, 5A-250 Vac, 5A - 30 Vdc (resistive load) |
pH Dosing Set Point | 0.00 to 14.00 pH |
pH Hysteresis Band | 0.00 to 14.00 pH |
Temperature Range | -9.9 to 120.0 °C |
Temperature Resolution | 0.1 °C |
Temperature Accuracy | ±0.5 °C |
Dosing Control | on/off |
Dosing Terminals | two electromechanical relay SPDT contact outputs, 5A-250 VAC, 5A - 30 VDC (resistive load), fuse protected |
Consent Relay | electromechanical relay SPDT contact outputs, 5A-250 VAC, 5A - 30 VDC (resistive load) (HI211YZ and HI212YZ), fuse protected |
Alarm Relay Set Point | electromechanical relay SPDT contact output, 5A - 250 VAC, 5A - 30 VDC (resistive load) fuse protected |
Alarm Relay Range | 0.00 to 14.00 pH |
Over Dosing Control | maximum relay ON time is adjustable from 1 to 60 minutes |
Analog Ouput Signal | 0 to 1 mA, 0 to 20 mA, 4 to 20 mA; 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC |
Voltage Output | ±5V power supply output for amplieifed electrodes |
Power Consumption | 15 VA |
Over Current Protection | 400 mA, 250V, fast fuse |
GLP | date, time, offset, slope and calibration buffers for the last calibration |
Power Supply | 230 VAC ±10% |
Environment | 0 to 50°C (32 to 122°F); RH max. 85% non-condensing |
IP Rating | IP54 |
Dimensions | 221 x 181 x 86 mm (8.7 x 7.1 x 3.4’’) |
Weight | 1.4 |
Ordering Information | Each HI21 model is supplied with instructions |
Voltage Output | ±5V power supply output for amplieifed electrodes |